[Features]
QX41-S1, QX42-S1
High speed input module that provides response time 0.1ms.
(Response time is variable using GX Developer Version5 or later.)
New positive common type 32-point and 64-point modules are now available, in addition to 16-point module
(QX40-S1).
QX42-S1 DC Input Module (Positive Common Type)
Type DC Input Module (Positive Common Type)
Specifications QX42-S1 Appearance
Number of input points 64 points
Isolation method Photocoupler
Rated input voltage 24VDC (+20/-15%, ripple ratio within 5%)
Rated input current Approx. 4mA
Input derating Refer to the derating chart.
ON voltage/ON current 19V or higher/3mA or higher
OFF voltage/OFF current 9.5V or lower/1.5mA or lower
Input resistance Approx. 5.6k
Set value 1 0.1 0.2 0.4 0.6 1
TYP. 0.05ms 0.15ms 0.30ms 0.55ms 1.05ms
OFF to ON
MAX. 0.12ms 0.20ms 0.40ms 0.60ms 1.20ms
TYP. 0.15ms 0.20ms 0.35ms 0.60ms 1.10ms
Response
time
ON to OFF
MAX. 0.20ms 0.30ms 0.50ms 0.70ms 1.30ms
Dielectric withstand voltage 560VAC rms/3 cycles (altitude 2000m (6557.38ft.))
Insulation resistance 10M or more by insulation resistance tester
By noise simulator of 500Vp-p noise voltage, 1 s noise width
Noise durability and 25 to 60Hz noise frequency
First transient noise IEC61000-4-4: 1kV
Level of protection IP2X
Wiring method for common 32 points/common (common terminal: 1B01, 1B02, 2B01, 2B02)
Number of occupied I/O points 64 (I/O assignment is set as a 64-point high speed input module)
Operation indication ON indication (LED), 32 point switch-over
Applicable connections 40-pin connector
Applicable wire size 0.3mm2 (For A6CON1)
Applicable wiring connector A6CON1, A6CON2, A6CON3, A6CON4 (Sold separately)
Applicable connector/terminal block
conversion module A6TBXY36, A6TBXY54, A6TBX70
5VDC internal current
consumption 90mA (TYP. all points ON)
Weight 0.18kg
QX42-S1
24VDC
4mA
QX42-S1
1: CPU parameter setting. (default: 0.2ms)
Response time is variable using GX Developer Version5 or later.
2: Pin number specifies the connectors; the first digit number “1” indicates left side connector and “2” indicates right side connector.
3: The LED displays X00 to X1F by turning the SW to F. It displays X20 to X3F by turning the SW to L.